97. Advanced settings
7. Advanced settings
To access the advanced settings submenu, first access the FD service function.
Numerical parameters are adjusted in the same way as Technical Service functions (see section 5.1).
C1
Safety self-adjustment. (1) Begin self-adjustment, (0) exit submenu without making any changes.
C2
Reduced Opening setting in 10% intervals between (1) =10% and (9)=90%. With some operators,
setting this value can additionally enable Reduced Opening.
C3
Set up Wi-Fi operating mode.
(1)=Wi-Fi O – switch o wireless connectivity.
(2)=Wi-Fi On – switch on wireless connectivity, enabling connection to an existing network.
(3)=e-SAT mode – switch on wireless connectivity for e-SAT.
This setting only works with operators that have Wi-Fi connectivity.
C4
Enable/disable auxiliary output. (1)=Inversion, change the operational status to the opposite of the
current one (for example, if it was enabled, it disables it);
(0) exit submenu without making any changes.
C5
Set up safety level during mode changes.
To edit the set value, the admin password is required.
(0)=OPEN – Validation required to enter OPEN mode.
(1)=CLOSE – Validation required to enter CLOSED mode.
(2)=OPEN and CLOSE – Validation required to enter both OPEN and CLOSED modes.
(3)=NOT SECURE – Does not require validation to change mode.
For escape routes, only settings 1 and 2 are permitted.
C6
Emergency exits. If error 11 (battery failure) occurs, disable door opening for 24 hours. To enable this
setting, the admin password is required.
(0)=RESTORE – Enable doors standard behaviour in case of battery failure;
(1)=DISABLE – Disable opening for at least 24 hours due to battery fault.
Normal operation will be restored if the battery fault has been resolved aer 24 hours of continuous use.
C7
Disable warning 22. Opening safety fault. To change this setting, the admin password is required.
(0)=DISABLE alarm; (1)=ENABLE side safety sensor monitoring and alarm (alarm 22).
C8
Disable warning 23. Closure safety fault. To change this setting, the admin password is required.
(0)=DISABLE alarm; (1)=ENABLE closure safety sensor monitoring and alarm (alarm 23).
C9
Allows temporary pairing of Pocket program switches. To enable pairing, the admin password is re-
quired. (0) Exit submenu without making any changes; (1)=START – Initiates a time window for pairing
new remote controls.
CA
RESET WIFI subsystem. To reset it, the admin password is required. (0) Exit submenu without making
any changes; (1)= RESET – Reset WIFI subsystem.
CB
RESET admin password. Reset admin password to default value (9999). Resetting requires the admin
password.
(0) Exit submenu without making any changes; (1)=RESET – Reset default value.
CC
Setting the function assigned to the “EXIT ONLY SS” mode key. To change the setting, the admin pass-
word is required; (0)=MODE – Pressing the key changes the mode to EXIT ONLY and cancels reduced
opening. (1)=Push button – Pressing the key emulates the behaviour of the internal push button input.
C0
Exit advanced settings submenu.