Technical Notice CSO/CPO V1.1 / 10.14 Page 75 / 86
Options 9
r2.2 Maximum set point -
c1.2 Minimum time between successive switch-ons
*(180 sec with a compressor, 30 sec with a
pump and 10 sec with a solenoid valve)
A0.2 Differential between alarms AL and AH *(=2°C, relative to AL.2 or AH.2)
AL.2 Low Temperature threshold alarm *(=10°C, relative to set point St2)
AH.2 High Temperature threshold alarm *(=10°C, relative to set point St2)
Ad.2 Low or high temperature alarms delay at start-up *(1,200 seconds)
AdL2 Low temperature alarm delay at start-up -
AdH2 High temperature alarm delay at start-up -
/c1.2 Probe calibration -
/3.2 ou C17.2
Refresh time of the sensor -
For all additional regulators, the incrementation rule governing the number after the ac-
ronym is applied. Ex: St3, rd3, r1.3, r2.3, c1.3, etc.
Code Description *Default value if not specified