Use the test function to check both the operation of the UPS and
the condition of the battery.
In AC operating mode,the level indicator will show the actual load
connected to this UPS normally.Press and hold the "Test" switch
on the front panel for more than 2 seconds,this UPS will enter into
testing mode. The battery will provide power to the load during this
period.Testing mode will check the status of battery and operation
of UPS,last for 10 seconds and transfer back to normal status
automatically.
Testing mode can not performed if the load connected is greater
than overload or the charging voltage is lower than
22Vdc (model:700W/1000VA) or 88Vdc (model:2100W/3000VA).
NOTE
Test
In battery backup mode, the level indicator will show the battery
capacity level and the alarm beeps normally. Press and hold the
" Test "switch on the front panel for more than 2 seconds. The
alarm will be silenced. The alarm can be activated again by
repeating the same procedure show in this paragraph. Under
silence model, press silence key , the alarm will be silent. When
it happens low battery , overload or second utility power cut off,
the alarm silence will be activated again.
Alarm Silence
To test the backup function, you may unplug the power cord of the UPS or simply press
the main switch button on the front panel. The UPS will beep once every 4 seconds and
the backup mode LED will turn on. You can press the main switch again to silence the
audible alarm.
2.5 Manual Simulation of Power Outage for the UPS
- 9-
Installation and Operating Instruction
AC Mode
The UPS delivers power to the loads derived from the utility and maintains proper
battery charge. It also regulates the output voltage to within a narrow range and
serves to isolate the load from surges and electrical noise brought by the utility wiring.
On-Battery Mode
The UPS operates on battery when the line voltage or frequency has fallen outside
the limits. Local users are alerted to this mode of operation by visual and audible
indicators. The UPS provides power to the load from the battery and through its
inverter and the output voltage and frequency of the UPS are regulated within a
narrow band.
2.4 Operation and Functional Test
Function
Panel Indicator
Switch On
press and hold the main switch on the front panel for more than 2
seconds until the "AC normal" green LED lights up/"Bypass"
Amber LED lights up/"Inverter "green LED lights up. The UPS will
perform a self-test every time it is switched on.