Leakage current: 10% ±3 digits
Voltage display: 3% ±3 digits ±0.5% of rated
voltage
Dielectric absorption Ratio (DAR): 60sec / 30sec ratio
Notes:
(1) All ranges measure from 0,00 MΩ upwards.
(2) Above specifications only apply when high quality
silicone leads are being used.
Continuity
EN61557 operating range: 0,01 Ω to 99,9 Ω (0 to 100 Ω on
analogue scale)
Accuracy: ± 2% ± 2 digits (0 to 100 Ω)
Open circuit voltage: 5 V ± 1 V
Test current: 205 mA (±5 mA) (0.01 Ω to 9.99 Ω)
20 mA (±1 mA) (10.0 Ω to 99.9 Ω)
Lead resistance zeroing: Up to 9,99 Ω
Buzzer:
Variable limit 1 Ω, 2 Ω, 5 Ω, 10 Ω, 20 Ω
Resistance
EN61557 operating range:
0,01 kΩ to 1000 kΩ (0 to 1 MΩ on analogue scale)
Accuracy: ±3% up to 50 kΩ then ±5% ±2 digits
Open circuit voltage: 5 V ±1 V
Short circuit current: 1.5 mA ±0.2 mA
Voltage range
0 to 600 V d.c. ± 2% ± 2 digits
10 mV to 600 V TRMS sinusoidal (40 – 400 Hz) ±2% ±2 digits
0 to 1000 V on analogue scale
Unspecified input level 0 – 10 mV (40 – 400 Hz)
For non sinusoidal waveforms additional specifications apply:
±3% ±2 digits 101 mV – 600 V TRMS and
±8% ±2 digits 10 mV – 100 mV TRMS
Default Voltmeter
Operates at >25 volts a.c. or d.c., on any range except OFF
Frequency: 15-400 Hz (15 Hz - 99,9 Hz) ±0.5% ±1 digit
(100 Hz to 400 Hz)
Power supply
5 x 1,5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline
NiMH rechargeable cells may be used.
Battery life
2200 insulation tests with duty cycle of 5 sec on 55 sec off