Specification
10
Maximum Load Capacitance: 1µF with less than ±0,1” pointer movement
Discharge: Up to 1µF capacitance is discharged from 1000V to less than 42,4 V in less than 4
secs
Safety Voltage Check
Voltage measurement: 0,1 V - 600 V a.c; the meter is RMS calibrated and average responding
Safety voltage indicator: Indicates the presence of d.c. voltages. Scaling is not the same as the a.c. meter.
True d.c. voltage equals scale reading divided by 2,22
Accuracy: 2,5% of full scale
Power Supplies
MJ159 and MJ160: Low voltage brushless a.c. generator. Cranking speed between 130 rpm and 170 rpm
MJ359: Dual operation low voltage brushless a.c. generator or 120 V 50/60 Hz mains
(line) supply
MJ459: Six IEC LR6 cells (AA) Battery life: not less than 1300 insulation
or Resistance range tests
MJ559: Dual operation 120 V 50/60 Hz mains (line) supply and rechargeable battery
Six Ni Cad cells (e.g. AA, NEDA 15 NC)
Safety: The instruments meet the requirements for double insulation to IEC 1010-1(1995),
EN 61010 (1995) to installation Category II, 300 V phase to earth (ground), 600 V
installation Category I
Flash Test: 6 kV a.c. r.m.s.