Operating Instructions MLR003R29
5.
6.
1.
2.
3.
4.
5.
6.
7.
Click Submit
Wait for Save and Apply to go red, and then click it
9.3 Pairing the Device with a Room Controller or Gateway
Devices will be accompanied with a spreadsheet containing the following information:
Device EUI
Join EUI
Application Key
The Device EUI is unique to the device and allows identification and communication via LoRaWAN.
The Application Key is randomly generated and the password to ensure secure communication.
 To pair a device to a MultiTech gateway:
In a web browser, navigate to the gateway IP address
Login to the gateway
(Only needs to be done once:)
LoRaWAN, Network Settings, Join Delay 5 seconds
LoRaWAN, Network Settings, Max Datarate 5 – SF7BW125
LoRaWAN, Key Management, click Add New
For each device, enter the following details, and then click OK:
Dev EUI (available in the spreadsheet)
App EUI (available in the spreadsheet)
App Key (available in the spreadsheet)
Class: A
Device Profile: LW102-OTA-EU868
Network Profile: DEFAULT-CLASS-A
Click Submit
Wait for Save and Apply to go red, and then click it
9.4 Mounting Position and OFF
In mounting position, the plunger inside the product’s valve adaptor is fully retracted, so that the unit
can be easily attached to a circulation valve. In mounting position, the product is OFF, preserving the
charge of the internal energy storage device. This makes it the preferred mode for shipping and storing.
How to enter mounting position from normal operation:
If the unit is attached to a valve, remove it
Hold the pen magnet to the micr°pelt logo on the product’s cover until a beep sounds
The unit will fail the reference run and consequently end up in mounting position
Upon delivery, all new units are in mounting position.
9.5 Attaching and Activating a unit
Before attempting to attach a unit to a valve, be sure it is in mounting position (refer to the above
section).
Check the target valve for contamination and leakage. If the valve requires it, do cleaning or service.
Then, place the aluminum connector of the product against the valve and secure it by using the ring nut.
Should the target valve not be of type M30 x 1.5, an adaptor is required.