MCAC-RTSM-2012-01 M-thermal Technical Manual (part 2)
A. "E0" "E8": Flow switch error
E0:Flow switch error( continuous for 3 times, and should be reset by switch off
the power supply )
E8:Flow switch error( one times)
1. The wire terminal is loose or connected incorrectly.
2. The wire circuit is short or open.
3. The pump is not running
4. The main control board's clamp diodes are short or open.
Check whether the wire
connected correctly or loose.
Is the wire circuit short or
Turn on the power supply. Is the
Main control board is
defective.
Properly connect the wire.
Check the wire connection or
replace the pump
Replace the main control
board.