M-thermal technical manual part 3
heating, “0” for sanitary heating priority, “1” for space cooling priority.
“1-2” Heat pump maximum running period for sanitary water tank heating: Specifies the
maximum time period during which sanitary water tank heating can be activated, even when the
target sanitary hot water temperature has not yet been reached..
“1-3” Solar heating priority: defines the priority sanitary hot water tank heating by solar kit “1” or by
heat pump & electric heater “0”.
Disinfection function
Apply only to installations with a sanitary hot water tank.
The disinfection function disinfects the sanitary hot water tank by periodically heating the sanitary
water to a specific temperature.
The disinfection function field settings must be configured by the installer according to national
and local regulations.
2-0 Operation interval: Day of a week, the sanitary water should be heated.
2-1 Status: Defines whether the disinfection function is turned on (1) or off (0).
2-2 Start time: Defines the time of the day at which the sanitary water should be heated.
2-3 Set point: Defines the hot water temperature to be reached when disinfection function.
2-4 Interval: Time period defining how long the set point temperature should be maintained.
Auxiliary heating source operation
3-0 Temperature difference: Defines the temperature difference between the set temperature
and the outlet temperature of indoor unit, above which the auxiliary heating source such as boiler
may be turned on.
3-1 Interval: Defines the time period after which the auxiliary heating source such as boiler
may be turned on.
3-2 Outdoor temperature: Defines the outdoor temperature below which the auxiliary heating
source such as boiler operation may be allowed.
3-3 Floor heating inlet temperature: Defines the temperature below which the under floor
heating may be allowed.
Electric heater & HP priority
Apply only to installations with a sanitary hot water tank.
4-0 Electric heater delay time: Defines the time period behind which the electric heater of the
sanitary hot water tank will be turned on.
4-1 Heat pump start temperature difference: Defines the temperature difference between set
temperature and water tank temperature, below which heat pump turning on will be allowed.
4-2 Set point correction for sanitary hot water tank temperature: The temperature difference
above the set temperature when the electric heater to be powered on.
Auxiliary heater operation
5-0 Auxiliary heater delay time: Defines the time period behind which the auxiliary heater of
the indoor unit will be turned on.
5-1 Auxiliary heater turn on temperature difference 1: Defines the temperature difference
between set temperature and water outlet temperature of indoor unit, below which one of the
auxiliary heaters will be turned on.
5-2 Auxiliary heater turn on temperature difference 2: Defines the temperature difference
between set temperature and water tank temperature, below which both of the auxiliary heaters
will be turned on.
5-3 Auxiliary heater turn on outdoor temperature: Specifies the outdoor temperature below
which the auxiliary heater may turn on.
Cooling and heating set point range

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea CE-LRSJF-V80/N1-310 and is the answer not in the manual?

Midea CE-LRSJF-V80/N1-310 Specifications

General IconGeneral
BrandMidea
ModelCE-LRSJF-V80/N1-310
CategoryWater Heater
LanguageEnglish

Related product manuals