MCAC-UTSM-201503 R410A Full DC Inverter Split Duct Type Technical Manual
50
2) L1/L4 troubleshooting
Step 1: Check the DC voltage between 1 and 2 terminal, the normal value should be 510V~580V, if the
voltage is lower than 510V, go to step 2.
Step 2: Check whether the wires of rectifier circuit are loose or not. If wires are loosen, fasten the wires. If
wires are OK, replace the main PCB.
1
2
3-Phase
bridge rectifier
Filter board