V6-i VRF 50/60Hz       
114     
Midea V6-i Series Service Manual
 
 
… flowchart continued from previous page 
Discharge part of the refrigerant. Add oil 
if it leaks during discharge 
System contains air or nitrogen
3
 
Flush all refrigerant then vacuum the 
system and recharge refrigerant. Add oil 
to the system if it leaks 
The condenser heat exchange is poor
4
 
Inspect the system and fix the error 
The high pressure side is blocked, caused 
by crushed or bent pipe or blocked EXV
5
 
Inspect the system and fix the error 
Inverter module has short-circuited
6
 
Replace the inverter module 
Compressor has malfunctioned
7
 
 
Notes:   
1.  An indoor load that is too large causes suction and discharge temperatures to be higher than normal. For normal system parameters refer to Table 6-3.4 
and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 
2.  Excess refrigerant causes discharge temperature to be lower than normal, discharge pressure to be higher than normal and suction pressure to be higher 
than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 
3.  Air or nitrogen in the system causes discharge temperature to be higher than normal, discharge pressure to be higher than normal, compressor current to 
be higher than normal, abnormal compressor noise and an unsteady pressure meter reading. For normal system parameters refer to Table 6-3.4 and 6-3.5 
in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 
4.  In cooling mode check outdoor heat exchangers, fans and air outlets for dirt/blockages. In heating mode check indoor heat exchangers, fans and air outlets 
for dirt/blockages. 
5.  High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to 
be lower than normal. For normal system parameters refer to Table 6-3.4 and 6-3.5 in Part 6, 3.2 “Normal Operating Parameters of Refrigerant System”. 
6.  Set  a  multi-meter  to  buzzer  mode  and  test  any  two  terminals  of  P  N  U  V  W  of  the  inverter  module.  If  the  buzzer  sounds,  the  inverter  module  has 
short-circuited. 
7.  The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances 
differ from these specifications, the compressor has malfunctioned.