V6-i VRF 50/60Hz       
62     
Midea V6-i Series Service Manual
 
Menu mode function: 
Table 5-2.3: Menu mode function 
All indoor units running in cooling mode 
If all indoor units in the system are the 2nd generation indoor units, all the indoor units 
will run in heating mode. Once there is one or more old indoor unit in the system, all the 
indoor units will run in forced cooling mode 
The system does not check the indoor units’ number. 
Only available for outdoor unit with two compressors. If one of the two compressors fails, 
the other compressor will keep running for up to 4 days and then stop automatically. 
It is only used in maintenance process. The digital display displays “R006”, and all solenoid 
valves are opened and EXVs are opened to the maximum steps.   
Cleaning history error codes 
Fahrenheit degree setting (
o
F) 
Celsius degree setting (
o
C) 
Exit auto power save mode 
Enter auto power save mode 
Auto snow-blowing mode 1 (customized) 
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for 
15 minutes and run for 2 minute 
Auto snow-blowing mode 2 (customized) 
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for 
30 minutes and run for 2 minute 
Exit auto snow-blowing mode 
The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button 
to change the VIP address and press OK button to confirm the specified VIP address.