2.5 E5: Abnormal power supply voltage 
 Digital display output 2.5.1
   
 
 Description 2.5.2
  Abnormal power supply voltage. 
  All units stop running. 
  Error code is only displayed on the unit with the error. 
 
 Trigger / recover condition 2.5.3
  Trigger condition: Outdoor unit power supply phase voltage < 165V. 
  Recover condition: Outdoor unit power supply phase voltage is > 180V. 
  Reset method: Resume automatically. 
 
 Possible causes 2.5.4
  Outdoor unit power supply voltage is abnormal or a phase is missing. 
  Loosened wiring within electric control box. 
  High voltage circuit error. 
  Main PCB damaged.