-i      V6-i VRF 50/60Hz 
    21 
Part 2 
- Component Layout
 and 
Refrigerant Circuits 
 
Key components: 
1.  Oil separator:   
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation 
efficiency is up to 99%. 
2.  Accumulator:   
Stores liquid refrigerant and oil to protect compressor from liquid hammering. 
3.  Electronic expansion valve (EXV): 
Controls refrigerant flow and reduces refrigerant pressure. 
4.  Four-way valve:   
Controls  refrigerant  flow  direction.  Closed  in  cooling  mode  and  open  in  heating  mode.  When  closed,  the  heat 
exchanger functions as a condenser; when open, the heat exchanger functions as an evaporator. 
5.  Solenoid valve SV4:   
Returns oil to the compressor. Opens once the compressor has run for 200 seconds and closes 600 seconds later and 
then opens for 3 minutes every 20 minutes. 
6.  Solenoid valve SV5:   
Enables  fast  defrosting  in  heating  mode  and  unloading  in  cooling  mode.  During  defrosting  operation,  opens  to 
shorten  the  refrigerant  flow  cycle  and  quicken  the  defrosting  process.  In  cooling  mode,  SV5  opens  when  outdoor 
ambient temperature is above 40
o
C or compressor frequency is below 41Hz.   
7.  Solenoid valve SV6: 
Allows refrigerant to bypass the expansion valves. Opens in cooling mode when discharge temperature exceeds the 
limit. Closed in heating mode and standby. 
8.  Solenoid valve SV7: 
Allows  refrigerant  to  return  directly  to  the  compressor.  Opens  when  indoor  air  temperature  is  close  to  the  set 
temperature to avoid frequent compressor on/off. 
9.  Solenoid valve SV8A / SV8B: 
Allows  refrigerant  from  plate  heat  exchanger  inject  directly  to  the  compressor.  SV8A  opens  when  compressor  A 
startup  and  closes  when  compressor  A  stop.  SV8B  delays  opening  when  compressor  B  startup  and  closes  when 
compressor B stop. 
10. Solenoid valve SV9: 
Balances compressor B pressure. Opens before compressor B startup and closed after compressor B running for 15 
seconds. Opens after compressor B stops 10s and keep opening 60s. 
11. High and low pressure switches:   
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or 
low pressure switches turn off, stopping the compressor. After 10 minutes, the compressor restarts.