V6-i VRF 50/60Hz       
86     
Midea V6-i Series Service Manual
 
2.9 xF1: DC bus voltage error   
 Digital display output 2.9.1
       
'x'  is  a  placeholder  for  the  compressor  system  (compressor  and  related  electrical  components),  with  1  representing 
compressor system A and 2 representing compressor system B. 
 
 Description 2.9.2
  1F1 indicates compressor A DC bus voltage error; 2F1 indicates compressor B DC bus voltage error. 
  All units stop running. 
  Error code is only displayed on the unit with the error. 
 
 Trigger / recover condition 2.9.3
  Trigger condition: DC bus voltage < 350V or DC bus voltage > 700V continuously for 10 seconds. 
  Recover condition: DC bus voltage goes back to normal. 
  Reset method: Restart automatically. 
 
 Possible causes 2.9.4
  Loosened wiring of the compressor inverter module. 
  Incorrect wiring of the reactor and DC bus wire. 
  Abnormal power supply. 
  Inverter module damaged.