V6-i VRF 50/60Hz       
98     
Midea V6-i Series Service Manual
 
 L2: DC bus high voltage protection 2.13.8
 
Note: 
1.  The normal DC  voltage between terminals P  and N on inverter module should be 450-650V.  When the voltage is higher than  700V, L2 
protection will be appeared.   
Figure 6-2.7: Inverter module terminals 
 
 
 
   
L2 protection
The power supply is abnormal
Check the power supply 
equipment
The DC bus voltage (P, N) is abnormal
1
Replace the 3-phase bridge 
rectifier
Replace the inverter module
No
No
Yes
Yes