7 Special Control 
7.1 Oil Return Operation 
In  order  to  prevent  compressors  from  running  out  of  oil,  the  oil  return  operation  is  conducted  to  recover  oil  that  has 
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that 
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display “d0”. 
 
Timing of oil return operation: 
  When the initial cumulative operating time reaches 140 minutes and then every 8 hours. 
 
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode. 
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode 
Control functions and states 
Fan  speed  controlled  according 
to discharge pressure   
Electronic expansion valve A 
Position  480  (steps)  or  3000 
(steps) 
Electronic expansion valve C 
Solenoid valve (oil balance) 
Solenoid valve (fast defrosting) 
Solenoid valve (EXV bypass) 
Solenoid  valve  (indoor  units 
bypass) 
Solenoid  valve  (inverter 
compressor A vapor injection) 
Controlled  according  to  inverter 
compressor A 
Solenoid  valve  (inverter 
compressor B vapor injection) 
Controlled  according  to  inverter 
compressor B 
Solenoid  valve  (inverter 
compressor B pressure balance) 
Open  before  compressor  B 
startup 
 
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode 
Control functions and states 
Remote controller setting 
Electronic expansion valve