Table 5-2.5: System check (continued) 
Parameters displayed on DSP2 
Actual value = value displayed × 10 
Actual value = value displayed × 10 
Address of VIP indoor unit 
Most recent error or protection code 
“--“ is  displayed if no error or protection events 
have occurred since start-up 
Notes: 
1.  Outdoor unit capacity setting: 
  0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP; 9: 26HP; A: 28HP; B: 30HP; C: 32HP. 
2.  Operating mode:   
  0: off; 2: cooling; 3: heating; 4: forced cooling. 
3.  The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 35 (fastest). 
4.  480P: steps = value displayed × 4; 3000P: steps = value displayed × 24. 
5.  Priority mode:   
  0: auto priority; 1: cooling priority; 2: VIP priority or voting priority; 3: heating only; 4: cooling only. 
6.  Silent mode:   
  0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode 1; 6: 
silent mode 2; 7: silent mode 3; 8: super silent mode 1; 9: super silent mode 2; 10: super silent mode 3; 11: super silent mode 4. 
7.  Static pressure mode:   
  0: standard static pressure; 1: low static pressure; 2: medium static pressure; 3: high static pressure; 4: super high static pressure. 
8.  Refrigerant quantity: 
  0: normal; 1: slightly excessive; 2: significantly excessive; 3: slightly insufficient; 4: significantly insufficient; 5: critically insufficient. 
9.  Power mode: 
  0: 100% capacity output; 1: 90% capacity output; 2: 80% capacity output; 3: 70% capacity output; 4: 60% capacity output; 5: 50% capacity output; 6: 
40%  capacity  output; 10:  auto power  save  mode,  100% capacity output;  11:  auto power  save  mode,  90%  capacity output;  12:  auto  power  save 
mode, 80% capacity output; 13: auto power save mode, 70% capacity output; 14: auto power save mode, 60% capacity output; 15: auto power save 
mode, 50% capacity output; 16: auto power save mode, 40% capacity output; 
 
 Digital display output 2.2.5
Table 5-2.6: Digital display output in different operating states 
Parameters displayed on DSP1 
Parameters displayed on DSP2 
The  number  of  indoor  units  in 
communication with the outdoor unit 
For single 
compressor units 
Running  speed  of  the  compressor  in 
rotations per second 
For dual 
compressor units 
Running  speed  of  compressor  B  in 
rotations per second 
Running  speed  of  compressor  A  in 
rotations per second