V6-i VRF 50/60Hz 
    35 
2 Stop Operation 
The stop operation occurs for one of the three following reasons: 
1.  Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with 
thermo off' operation and an error code is displayed on the outdoor unit digital displays. 
2.  The system stops when the set temperature has been reached. 
 
3 Standby Control 
3.1 Crankcase Heater Control 
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped. 
The  crankcase  heater  is  controlled  according  to  outdoor  ambient  temperature  and  discharge  temperature.  When  the 
outdoor ambient temperature is above 40°C, the crankcase heater is off; when the outdoor ambient temperature is below 
35°C, the crankcase heater is controlled according to discharge temperature. Refer to Figures 3-3.1 and 3-3.2. 
 
Figure 3-3.1: Crankcase heater controlled according to outdoor ambient temperature 
 
Figure 3-3.2: Crankcase heater controlled according to discharge temperature 
 
   
Ambient temperature < 35
 o
C   
Ambient temperature > 40
 o
C 
Crankcase heater is controlled according to discharge temperature 
Discharge temperature < 40
 o
C   
Discharge temperature > 50
 o
C