MCAC-VTSM-2014-04 R410A DC Inverter V4 Plus 50Hz
Troubleshooting 93
Outdoor Temp. sensor error
Low-voltage power protection
Discharge Temp. sensor error
Air discharge<15 degree, at the same time
pressure higher than 3.0MPa, then will alarm,
need to power off for recovery
COMM. Error(IR341&MC9S08AC128)
COMM. Error(0537&MC9S08AC128)
3 times of P6 in 60 minutes
Not recoverable unit re-power on
3 times of P2 protection in 60 minutes
Not recoverable unit re-power on
3 times of P4 protection in 100 minutes
Not recoverable unit re-power on
Qty. of indoor units can’t match
Indoor unit lost over 3 minutes; can not recover,
unit recover the unit Qty.
High pressure sensor error
Air discharge pressure Pc<=0.3Mpa
Not recoverable unit re-power on
Outdoor unit capacity setting error
Inverter compressor top Temp. protection
After 3 times P2 protection in 60 minutes will
report H5
Inverter compressor current protection
High discharge Temp. protection
After 3 times P4 protection in 100 minutes will
report H6
High condenser Temp. protection
Inverter module protection
No.X fixed compressor current protection
X stand for the fixed compressor No.
Protection of insufficient in degree of superheat of
compressor discharging
3 times of PP protection in 150 minutes
After 3 times P9 protection in 60 minutes will
report H9
Compressor module protection
DC bus low voltage protection
DC bus high voltage protection