CMR CARD
18.4 SP1
BC_GB18
18-2 SEPRI CMR06 CARD FOR D.C MOTOR CONTROL
Operations required :
- To check the conditions for the right working of the card;
voltage values required:
- 36 V a.c between terminals 1 and 2 of 10-terminal board with 10 terminals
If the fuse is okey, these are the conditions to obtain the voltage of 24 V d.c at the output between terminals 1
and 2 of the terminal board with 10 terminals by sending high voltage 110 V to channel A or B of the terminal
board with 8 terminals.
Otherwise replace the card and send the defective one to SCM Technical Service .
3 leds are present on the cards:
- red light lit: card fuse interrupted
- green light lit: motor overload cutout intervention
- yellow light lit: motor overload cutout intervention.
Vda = Volt (alternate current)
Vdc = Volt (direct current)