EasyManua.ls Logo

Mircom FA-103 - Wiring Tables and Information

Mircom FA-103
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FA-106 Installation and Operation Manual
9
Wiring Tables and Information
Table 1: Wiring table for detection zone
Table 2: Wiring table for bells and horns
Signal circuits are rated for 1.25 amperes each.
Note: The panel must be wired by a certified electrician in accordance with CEC part 1, section 32 “Fire
alarm systems, fire pumps, and carbon monoxide alarms”.
Wire Gauge Maximum Wiring Run to Last Device (ELR)
(AWG) ft. m
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
Note: Maximum loop resistance should not exceed 100 ohms.
Total Signal
Load
Maximum Wiring Run to Last Device (ELR)
Max Loop
Resistance
18AWG 16AWG 14AWG 12AWG 0hms
Amperes ft. m ft. m ft. m ft. m Ohms
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 750 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.25 109 33 171 52 277 84 450 137 1.4
Note: Maximum voltage drop should not exceed 1.8 volts.

Related product manuals