Configuration with the CFG-300 LCD Service Tool
Command Menu/FA-300 Config/Features/
18. Auto General Alarm Timer
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 15 Min
[ ] 20 Min
[ ] 30 Min
General alarm Timer
This function is used for two-
stage systems only. This function
sets the time period for automatic
evacuation.
Command Menu/FA-300 Config/Features/
19. Common Alarm Relay
Operation
[ ] BOTH STAGES-
>Default
[X] SECOND STAGE ONLY
Alarm relay second
stage
Use this menu to allow the
Common Alarm Relay to operate
in second stage only or to
operate in both stages.
Command Menu/FA-300 Config/Features/
20. First Stage LED
[X] DISABLE->Default
[ ] ENABLE
When disabled, the AUTOMATIC
ALARM SIGNAL CANCEL LED
does not illuminate during the
first stage alarm.
When enabled, the AUTOMATIC
ALARM SIGNAL CANCEL LED
flashes at the fast rate during the
first stage alarm.
Note: If this option is enabled,
then the panel is outside of UL/
ULC certification acceptability.
The authority having jurisdiction
must approve this selection.
Table 14 Feature Config menu
Feature Default
Name in the
FA-300
Configuration Utility
Description
Auto Gen-Alarm Timer
[X] DISABLE
Common Alm Rly. Oper
[X] SECOND STAGE
1st stage LED indic.
[X] DISABLE

Table of Contents

Other manuals for Mircom FA-301-12LDW

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FA-301-12LDW and is the answer not in the manual?

Mircom FA-301-12LDW Specifications

General IconGeneral
BrandMircom
ModelFA-301-12LDW
CategoryControl Panel
LanguageEnglish

Related product manuals