NOT TO BE USED FOR INSTALLATION PURPOSES.
ALC-198S Single Analog Loop Controller Module
The ALC-198S Single Analog Loop Controller Module
provides an additional analog loop to the FX-2000
consisting of 99 Analog Sensors and 99 Addressable
Modules. The ALC-198S occupies one module slot in
the FX-2000 main or expander chassis.
Adder Auxiliary Modules
Adder Hardwire Modules
DM-1008A Eight Initiating Circuit Module
The DM-1008A provides 8 Class B (Style B) or 4 Class
A (Style D) Initiating Circuits congurable for Alarm,
Supervisory or Trouble zones. The DM-1008A occupies
one module slot in the FX-2000 main or expander chassis.
PR-300 Polarity Reversal/City Tie Module
The PR-300 Polarity Reversal/City Tie Module provides
the system with a supervised City Tie (24 VDC/200 mA
max.) and Polarity Reversal connection (24 VDC (open
circuit), 8 mA max. (shorted)). The PR-300 mounts in
the FX-2000 main chassis.
RM-1008A Eight Relay Circuit Module
The RM-1008A provides the FX-2000 with 8 individual
congurable relays per module. Each relay provides
one Form C contact rated at 28 VDC @1 Amp
(resistive load). The RM-1008A occupies one module
slot in the FX-2000 main or expander chassis.
SGM-1004A Four Indicating Circuit Module
The SGM-1004A provides 4 Class A/B (Style Z/Y)
Indicating Circuits configurable as Silenceable or
Non-Silenceable. Each Indicating Circuits is rated
at 1.7 Amps. Each of the indicating circuits have
individual signal silence inputs which are jumper
selectable. The SGM-1004A occupies one module
slot in the FX-2000 main or expander chassis.
ALC-H16 Hardwire Loop Controller Module
The ALC-H16 Hardwire Loop Controller Module allows the
FX-2000 to support an additional sixteen (16) conventional
hardwire adder modules. The hardwire modules consist
of the DM-1008 Eight Initiating Circuit Module, SGM-
1004 Four Indicating Circuit Module and the RM-1008
Eight Relay Circuit Module. The ALC-H16 occupies one
module slot in the FX-2000 main or expander chassis.
ALC-396S Dual Analog Loop Controller Module
The ALC-396S Dual Analog Loop Controller Module
provides two additional analog loops to the FX-2000
consisting of 99 Analog Sensors and 99 Addressable
Modules per loop. The ALC-396S occupies one module
slot in the FX-2000 main or expander chassis.
Adder Loop Controller Modules
CAT. 5910
page 4 of 10
UDACT-300A Digital Alarm Communicator Module
The UDACT-300A Digital Alarm Communicator Module
allows the FX-2000 to transmit addressable point information
to a central station. The UDACT-300A can be congured
locally via the on-board keypad and the CFG-300
Conguration Tool or with a UIMA programming tool and a
computer with an available serial or USB port. The UDACT-
300A occupies one module slot in the FX-2000 main or
expander chassis.