EasyManua.ls Logo

Mitsubishi Electric MELSEC FX Series - FX 0 N -485 ADP and FX 0 N -485 ADP

Mitsubishi Electric MELSEC FX Series
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FX communication
Wiring 3
3-10
3.4.2 FX
0N
-485ADP and FX
0N
-485ADP
1 ) One-pair Wiring
Note:
*1 Connect the terminal FG to the ground terminal of a programmable controller grounded
with a resistance of 100
or less (Class D grounding). If the programmable controller is
not equipped with a ground terminal, connect the terminal FG directly to a ground with the
resistance of 100
or less (Class D grounding).
2 ) Two-pair Wiring
Note:
*1 Connect the terminal FG to the ground terminal of a programmable controller grounded
with a resistance of 100
or less (Class D grounding). If the programmable controller is
not equipped with a ground terminal, connect the terminal FG directly to a ground with the
resistance of 100
or less (Class D grounding).
RDB
RDA
SDA
SDB
SDA
Terminating
resistor
110
FX
0N
-485ADP
Terminating
resistor
110
RDA
RDB
LINK
SG
SDB
LINK
SG
FG *1FG
FX
0N
-485ADP
RDB
RDA
SDA
SDB
SDA
FX
0N
-485ADP
Terminating
resistor
330
FX
0N
-485ADP
Terminating
resistor
330
RDA
RDB
LINK
SG
SDB
LINK
SG
FG *1FG
Terminating
resistor
330
Terminating
resistor
330

Table of Contents

Other manuals for Mitsubishi Electric MELSEC FX Series

Related product manuals