FX communication
N:N network 4
4-3
4
4.2 Setting
N:N settings become valid when the program is run or when the power of the programmable
controller is turned ON.
4.2.1 Setting the Station No. (D8176)
Set a value 0 to 7 to the special data register D8176.
4.2.2 Setting the Total Number of Slave Stations (D8177)
Set value Description
0 Master station
1 to 7
Slave station No.
Example: 1 is slave station No.1, 2 is slave station No.2
Set a value 1 to 7 to the special data register D8177. (Default = 7)
This setting is not required for the slave station.
Set value Description
1
1 slave station
2
2 slave stations
:
:
7
7 slave stations