FX communication
Communication format 6
6-3
6
6.4 Example of setting program
When setting the contents shown on the left, perform programming as follows.
M8002
0000 1100 1000 1110
b15 b0
0 C 8 E
D8120 =
FNC 12
MOV
H0C8E D8120
Data length 7 bits
Parity Even
Stop bit 2 bits
Baud rate 9600 bps
Protocol No protocol
Header No used
Terminator No used
Control line Normal mode 1