5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected
5.2 System to Which Multiple Safety CPUs are
Connected
This section describes a configuration example of a safety application performs safety communications using three Safety
CPUs.
System configuration
This section describes a safety application using the following system configuration.
In the figure above, "N" means network number, while "S" means station number. For example, "N1" means network number
1, while "S0" means station number 0.
*1 This sets parameters and programs.
*2 They are safety input device such as emergency stop switch, safety switch, light curtain, laser scanner, and mat switch.
*3 They are safety output device such as safety relay and MC.
*4 They are general input device such as reset switch, start switch, and stop switch.
The following table shows definitions of the symbols used in this chapter.
Symbol Definition
CCIEF master (A-0)
(A = 2, 3, 4)
MELSEC iQ-R series CC-Link IE Field Network master/local module (network number 2, 3, 4, station number 0)
This is used when communicating with safety remote I/O module.
CCIEF remote (A-1)
(A = 2, 3, 4)
Safety remote I/O module (network number 2, 3, 4, station number 1)
This is a safety remote I/O module to be used for safety input/output.
CCIEF remote (A-2)
(A = 2, 3, 4)
Standard remote I/O module (network number 2, 3, 4, station number 2)
This is a standard remote I/O module to be used for standard input/output.
CCIEF programmable controller master (1-
0)
MELSEC iQ-R series CC-Link IE Field Network master/local module (network number 1, station number 0)
This is used when communicating between Safety CPUs.
CCIEF programmable controller local (1-1) MELSEC iQ-R series CC-Link IE Field Network master/local module (network number 1, station number 1)
This is used when communicating between Safety CPUs.
CCIEF programmable controller local (1-2) MELSEC iQ-R series CC-Link IE Field Network master/local module (network number 1, station number 2)
This is used when communicating between Safety CPUs.
GX Works3*
1
Safety programmable
controller (1)
Standard input*
4
Safety input*
2
Safety output*
3
CC-Link IE Field Network
CCIEF master (2-0)
N2, S0
CCIEF
remote (2-1):
SR_M2IO1
N2, S1
CCIEF
remote (2-2):
R_M2IO2
N2, S2
CCIEF programmable
controller master (1-0)
N1, S0
CCIEF master (3-0)
N3, S0
CCIEF master (4-0)
N4, S0
Safety programmable
controller (2)
Standard input*
4
Safety input*
2
Safety output*
3
CCIEF
remote (3-1):
SR_M3IO1
N3, S1
CCIEF
remote (3-2):
R_M3IO2
N3, S2
CCIEF
programmable
controller local (1-1)
N1, S1
CCIEF
programmable
controller local (1-2)
N1, S2
Safety programmable
controller (3)
Standard input*
4
Safety input*
2
Safety output*
3
CCIEF
remote (4-1):
SR_M4IO1
N4, S1
CCIEF
remote (4-2):
R_M4IO2
N4, S2