5  SAFETY APPLICATION CONFIGURATION EXAMPLES
5.1  System Configured by a Safety CPU
73
5
Setting standard inputs
Wiring
Wiring example of reset switch, start switch, and stop switch to CC-Link IE Field Network remote I/O module (NZ2GF2B1-
16D)
Example of parameter setting
Item Description
Input response time 10ms
Output HOLD/CLEAR setting CLEAR
Cyclic data update watch time setting 0
Mode switch Automatical judgment mode
Initial operation setting With initial processing
Synchronous input timing acquisition function Invalid
Input off delay setting X0 to XF 0
A1 +24V
A2 24G
A3 FG
16 XF
17 COM
18 COM
1X0
2X1
3X2
Terminal block for 
power supply and FG
24VDC
CCIEF remote (2)
NZ2GF2B1-16D
24VDC
Terminal block for input
Reset switch (NO)
Start switch (NO)
Stop switch (NC)