400
21 INDEPENDENT/LINKED OPERATION OF INTERFACE
21.2 Setting and Data Flow of Interlink Operation
Setting example for MELSOFT connection via C24
Examples of the parameter settings for MELSOFT connection via C24 are as shown below.
Setting at station No.0
Setting at station No.1
Setting item Setting content
CH1 CH2
Basic
settings
Transmission
setting
Test mode setting
Communication protocol setting MELSOFT Connection
Communication speed setting 115200 bps 115200 bps
Transmission setting Operation setting Independent Interlink
Data bit 8 8
Parity bit Yes Yes
Odd/even parity Odd Odd
Stop bit 1 1
Sum check code Yes Yes
Online change Enable Enable
Setting change Enable Enable
Station number setting (CH1, 2 in common: 0 to 31) 0
Setting item Setting content
CH1 CH2
Basic
settings
Transmission
setting
Test mode setting
Communication protocol setting Set depending on the use MC protocol (format 5)
Communication speed setting 115200 bps
Transmission setting Operation setting Independent
Data bit 8
Parity bit Yes
Odd/even parity Odd
Stop bit 1
Sum check code Yes
Online change Enable
Setting change Enable
Station number setting (CH1, 2 in common: 0 to 31) 1
RS-232 RS-485
Station 0
Station 1