27 TROUBLESHOOTING
27.4 Error Code List
477
27
7D11H Protocol
simultaneous
execution error
The CPRTCL instruction
and 'CH1 protocol
execution request' (Y3) or
'CH2 protocol execution
request' (YA) were
executed simultaneously
on the same channel.
CHn
ERR.
Correct the program not to
execute the CPRTCL
instruction and 'CH1 protocol
execution request' (Y3)/'CH2
protocol execution request'
(YA) simultaneously on the
same channel.
7D12H Send monitoring
time timeout error
Send monitoring time has
timed out.
Although the transmission
was retried the specified
number of retries, it did not
succeed.
CHn
ERR.
Check if the transmission is
interrupted due to some
reasons such as DTR control.
Check whether the CS signal
is ON.
Check if the cables are
disconnected.
7D13H Receive wait
timeout error
Receive wait time has
timed out.
CHn
ERR.
Check if the reception is
interrupted due to some
reasons such as DTR control.
Check if the cables are
disconnected.
Check if any errors occur on
the target device side.
Using the circuit trace function
(send/receive data monitoring
function), check if;
Transmissions from the target
device are interrupted.
Any data are missing due to a
data reception error.
The data (packet) sent from
the target device is incorrect.
7D14H Response
monitoring
timeout error
Response monitoring time
(timer 1) has timed out
during data transmission.
Data to be sent to the
target device was not
obtained from the CPU
module within the
response monitoring time
(timer 1).
CHn
ERR.
Increase the setting value for
the response monitoring time
(timer 1). (Default: 5 seconds)
If an error occurred on the
CPU module, refer to the
following manual.
(MELSEC iQ-R CPU
Module User's Manual
(Application))
7D15H Response
monitoring
timeout error
Response monitoring time
(timer 1) has timed out
during data reception.
Data received from the
target device was not
stored into the CPU
module within the
response monitoring time
(timer 1).
CHn
ERR.
Increase the setting value for
the response monitoring time
(timer 1). (Default: 5 seconds)
If an error occurred on the
CPU module, refer to the
following manual.
(MELSEC iQ-R CPU
Module User's Manual
(Application))
7D1
6H Protocol cancel
request error
A cancel request was
accepted during protocol
execution, and the
CPRTCL instruction was
completed abnormally.
The CPRTCL instruction
was completed
abnormally because
protocol setting data were
written during CPRTCL
instruction execution.
The STOP RUN
operation was performed
on the CPU module.
CHn
ERR.
Check the cancelled
Predefined protocol in the
CPRTCL instruction's control
data (number of executions),
and eliminate the cause of the
cancellation.
Clear the error information by
the 'Error initialization request'
(YE) as necessary.
To prevent coincidental
execution of the CPRTCL
instruction, set the CPU
module in the STOP state
before writing the protocol
setting data.
Execute the CPRTCL
instruction again.
Error code
(hexadecima
l)
Error Description Signal
name
Corrective action Protocol
MC Nonpr
ocedu
ral
Bidire
ctiona
l
Prede
fined

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-RJ71C24-R4

Related product manuals