2 - 82
2 SYSTEM CONFIGURATION
(b) Input/output
Item Specifications
Number of input points
32 points
2 lines
(PLC CPU control 32 points + Motion CPU control 32 points,
Safety input 20 points
2 lines,
Feedback input for output 12 points 2 lines
)
Input isolation method Photocoupler
Rated input voltage 24VDC (10%, ripple rate within 5%)
Rated input current Approx. 4mA
Input resistance Approx. 8.2k
ON voltage/ON current 20V or more/3.0mA or more
OFF voltage/OFF current 5V or less/1.7mA or less
Input response time
PLC CPU control I/O : 10ms (initial value of digital filter)
Motion CPU control I/O : 15ms (CR filter)
Input common method
32 points/common
(PLC I/O and Motion I/O are separated.)
Input type Type 1, Current sinking
Number of output points
12 points
2 lines
(PLC CPU control 12 points + Motion CPU control 12 points)
Output isolation method Photocoupler
Rated load voltage 24VDC (10%)
Maximum load current
(0.1A
8 points, 0.2A 4 points) 2 lines
Common current: 1.6A or less for each connector
Maximum inrush current 0.7A 10ms or less (0.2A output pin: 1.4A 10ms or less)
Output response time 1ms or less
Output common method 12 points/common (PLC I/O and Motion I/O are separated.)
Output type Current sourcing
External power supply 24VDC (10%, ripple rate within 5%)
Operation indicator (input/output) ON indication (LED) (indicates PLC CPU's 32 points)
Communication with PLC CPU Parallel bus communication (Via main base unit)
Communication with Motion CPU Serial communication (RS-485), Q173DSXYCBL M cable use
Applicable wire size
0.3mm
2
Applicable connector for the
external connection
A6CON1 (Attachment), A6CON2, A6CON3, A6CON4 (Optional)
Connector/terminal block
conversion module
A6TBXY36 (Optional),
FA-LTB40P (Optional: Mitsubishi Electric Engineering Co., Ltd. make)
Cable for connector/terminal block
conversion module
AC50TB (included with A6TBXY36),
FA-CBL FMV-M (included with FA-LTB40P)
Number of modules Up to 3 modules