EasyManua.ls Logo

Mitsubishi Electric Melsec-Q172DCPU - Page 215

Mitsubishi Electric Melsec-Q172DCPU
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 - 26
6 INSPECTION AND MAINTENANCE
(h) Flowchart for when "BT " displays on 7-segment LED
"BT1" or "BT2" displays when the battery voltage is lowered.
"BT1" or "BT2" displays at the following cases.
• BT1: Battery voltage 2.7V or less
• BT2: Battery voltage 2.5V or less
The following shows the flowchart for when "BT1" or "BT2" displays on
7-segment LED.
A hardware fault
Explain the error symptom and get
advice from our sales representative.
END
YES (SM58, SM51 OFF)
NO (SM58 or SM51 ON)
"BT " displays on 7-segment LED
Replace the battery.
(Refer to Section 6.5.2)
Does "BT "
disappear on 7-segment
LED? (Confirm ON/OFF by
monitoring SM )
REMARK
If SM51, SM58 turns on, the contents of the programs, parameters, motion device(#),
latch range device and absolute position data cannot be guaranteed.
It is recommended to back-up the data periodically.