10 - 2
10. MAINTENANCE AND INSPECTION
10.1 Daily Inspection
Dairy inspection items recommended are shown in Table 10.1.
Table 10.1 Dairy inspection
Item Check item Content of inspection Judgement Action
1
Installation condition of the 
base unit
Confirm if installation 
screws are not loose or 
cover is not detached.
It is installed securely. Retighten the screw.
2
Installation condition of the 
I/O modules
Confirm if the module 
mounting screw is firmly 
tightened.
The mounting screws 
are firmly tightened.
Firmly tighten the 
module mounting 
screw.
3 Connection condition
Loosening of terminal 
screw
No loosening.
Retighten the terminal 
screw.
Proximity of solderless 
terminals.
There is an 
appropriate distance.
Correct the distance.
Connector areas of 
extension cable
No loosening at 
connectors.
Retighten the 
connector fixing 
screw.
4
LEDs on the main module
POWER LED Confirm it is on.
The LED is on.
(Faulty if it is off.)
Refer to Section 
11.2.2.
MODE LED Confirm it is on.
The LED is on.
(Faulty if it is off.)
Refer to Section 
11.2.3.
RUN LED
Confirm it is on in the 
"RUN" state.
The LED is on.
(Faulty if it is off or 
flickering.)
Refer to Section 
11.2.4
Section 11.2.5.
ERR. LED
Confirm it is on when an 
error occurs.
This LED is off.
(On when an error 
occurs.)
Refer to Section 
11.2.6
Section 11.2.7.
Input LED
Confirm if it correctly 
turns on and off.
The LED is on when 
input is on, and off 
when input is off.
(Faulty other than the 
above.)
Refer to Section 
11.4.1.
Output LED
Confirm if it correctly 
turns on and off.
The LED is on when 
output is on, and off 
when output is off.
(Faulty other than the 
above.)
Refer to Section 
11.4.2.