App - 39
APPENDICES
Table App.2.2 Special Register List (continued)
Number Name Description Details Applicable CPU
*1
D9116
I/O module
verify error
Bit pattern in units of
16 points of verify
error modules
When I/O modules, of which data are different from
those entered at power-on, have been detected, the I/
O module numbers (in units of 16 points) are entered in
bit pattern. (Preset I/O module numbers when
parameter setting has been performed.)
Turns on all the bits corresponding to the I/O module
number (in units of 16 points) in input/output points
occupied by the modules on modules with more than
16 input/output points.
I/O module verify check is executed also to remote I/O
station modules.
(If normal status is restored, clear is not performed.
Therefore, it is required to perform clear by user
program.)
Usable with all
types of CPUs
Only remote
I/O station
information
is valid for
A2C.
*1
D9117
*1
D9118
*1
D9119
*1
D9120
*1
D9121
*1
D9122
*1
D9123
*1
D9116
I/O module
verification
error
Bit pattern of
verification error
module
When an I/O module different from the I/O module data
registered during power-on is detected, this register
indicates the bit pattern of the I/O module number.
Dedicated to
A0J2H.
D9124
Annunciator
detection
quantity
Annunciator
detection quantity
When one of F0 to 255 (F0 to 2047 for AnA and AnU)
is turned on by SET F 1 is added to the contents of
D9124. When RST F or LEDR instruction is
executed, 1 is subtracted from the contents of D9124.
(If the INDICATOR RESET switch is provided to the
CPU, pressing the switch can execute the same
processing.)
Quantity, which has been turned on by SET F is
stored into D9124 in BIN code. The quantity turned on
with SET F is stored up to "8."
Usable with all
types of CPUs.
D9116
D9117
D9123
15 14 12 1113 10 9 8 6
5
432107
00 00000000000
0
00000000000000
000 000 000 0000
Indicates I/O module verify error.
0
0
0
0
1
XY
7E0
1
XY
180
1
XY
0
(Example) On a module with 64 points attached to
slot 0, b3 to b0 turn on when an error is
detected.
00
b15
D9116
b8 b7 b6 b5 b4 b3 b2 b1
0 is fixed.
Indicates the module
for setting switch 0.
Indicates the module
for setting switch 1.
Indicates the module
for setting switch 2.
Indicates the module
for setting switch 3.
Indicates the module for setting
switch 4 or the module for
extension base unit slot 0.
Indicates the module for setting
switch 5 or the module for
extension base unit slot 1.
Indicates the module for setting
switch 6 or the module for
extension base unit slot 2.
Indicates the module for setting switch 7 or
the module for extension base unit slot 3.