311
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.3 List of error codes (1000 to 1999)
1009
[MAIN CPU DOWN]
The voltage waveform that is outside the
specification is applied to the power supply
module, and an error is detected.
A failure was detected on the power supply
module, CPU module, main base unit, extension
base unit or extension cable.
When using the redundant base unit, the
redundant power supply module failure in both
systems and/or the redundant base unit failure
are detected.
Collateral information
Common information: -
Individual information: Failure information
(QnUDVCPU only)
Diagnostic timing
Always
Correct the voltage waveform applied to
the power supply module.
Reset the CPU module and run it again. If
the same error code is detected again, the
cause is a failure of the power supply
module, CPU module, main base unit,
extension base unit, or extension cable.
Please consult your local Mitsubishi
representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
QnU
[CPU UNIT DOWN]
A failure was detected on the power supply
module or CPU module.
The voltage waveform that is outside the
specification is applied to the power supply
module, and an error is detected.
Collateral information
Common information: -
Individual information: Failure information
Diagnostic timing
Always
Correct the voltage waveform applied to
the power supply module.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the power
supply module or CPU module. Please
consult your local Mitsubishi
representative.
LCPU
1010
[END NOT EXECUTE]
Entire program was executed without the
execution of an END instruction.
When the END instruction is executed it is read
as another instruction code, e.g. due to noise.
The END instruction has been changed to
another instruction code somehow.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
When an END instruction executed
Take noise reduction measures.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
1020
[SFCP. END ERROR]
The SFC program cannot be normally terminated
due to noise or other reason.
The SFC program cannot be normally
terminated due to noise or any similar cause.
The SFC program cannot be normally
terminated for any other reason.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
When SFC program is executed
Take noise reduction measures.
Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q
00J/Q00/Q01
QnPH
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU