462
SM280 CC-Link error
OFF: Normal
ON: Error
This relay turns on if a CC-Link error is
detected in any of the CC-Link modules
mounted, and turns off when the
condition returns to normal.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
SM310
Mounting status of
RS-232, RS-
442/485 adapter
OFF: No adapter
mounted
ON: RS-232 or RS-
422/485 adapter
mounted
This relay stores whether the RS-232 or
RS-422/485 adapter is mounted or not.
The mounting status of the RS-232 or
RS-422/485 adapter is checked during
the initial processing, and if it is mounted,
this relay turns on.
The on/off status set during the initial
processing is held until the CPU module
is powered off and on again or is reset.
S (Initial) New LCPU
SM315
Communication
reserved time
delay
enable/disable flag
OFF: Without delay
ON: With delay
This flag is enabled when the time
reserved for communication
processing is set in SD315.
Turns ON to delay the END processing
by the time set in SD315 in order to
perform communication processing.
(The scan time increases by the period
set in SD315.)
Turns OFF to perform the END
processing without a delay of the time
set in SD315 when there is no
communication processing. (Defaults
to OFF)
U New Q00J/Q00/Q01
SM319
Automatic CC-Link
start
OFF: Not activated
ON: Activated
This relay indicates whether the CC-
Link module is started and all the data
are refreshed by the automatic CC-
Link start function.
This relay is on when all the data are
refreshed by the automatic CC-Link
start function.
Then the automatic CC-Link start
function is not activated, or when the
refresh device range is insufficient, this
relay is turned off. (If the refresh device
range set for the automatic CC-Link
start function is insufficient, all of the
refresh is stopped.)
S (Initial
processing
and status
change)
New LCPU
SM320
Presence/absence
of SFC program
OFF: SFC program
absent
ON: SFC program
present
This relay is on if an SFC program is
registered.
This relay turns off if no SFC program
is registered.
S (Initial) M9100
Q00J/Q00/Q01
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
SM321
Start/stop SFC
program
OFF: SFC program not
executed (stop)
ON: SFC program
executed (start)
The same value as in SM320 is set as
the initial value. (This relay turns on
when an SFC program is registered.)
Turning off this relay stops SFC
program execution.
Turning on this relay restarts SFC
program execution.
S (Initial)/U
M9101 format
change
Q00J/Q00/Q01
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
SM322
SFC program start
status
OFF: Initial start
ON: Resume start
In the SFC tab of "PLC Parameter",
"Initial start" is set for "SFC program start
mode".
At initial start:OFF
At continued start:ON
S (Initial)/U
M9102 format
change
Q00J/Q00/Q01
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
Number Name Meaning Explanation