EasyManua.ls Logo

Mitsubishi Electric Q13UDVCPU - Page 502

Mitsubishi Electric Q13UDVCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
500
SM1887 CH1 error
OFF: No error
ON: Error
This relay turns on if the CH1 error
occurs.
This relay turns off when an error cause is
removed and CH1 error reset command is
turned on.
S (Every
END
processing)
New LCPU
SM1888 CH1 warning
OFF: No warning
ON: Warning
This relay turns on if a warning occurs in
CH1.
This relay turns off when a warning cause
is removed and CH1 error reset command
is turned on.
S (Every
END
processing)
New LCPU
SM1890
CH1
coincidence
signal No.1
reset command
Resets CH1 counter
value coincidence No.1.
This relay is turned on to reset CH1
counter value coincidence No.1.
The command is valid while this relay is
on.
The on time must be held for at least 2ms.
UNewLCPU
SM1891
CH1
coincidence
signal No.2
reset command
Resets CH1 counter
value coincidence No.2.
This relay is turned on to reset CH1
counter value coincidence No.2.
The command is valid while this relay is
on.
The on time must be held for at least 2ms.
UNewLCPU
SM1892
CH1
coincidence
output enable
command
Controls outputs from
CH1 coincidence output
No.1 and No.2 terminals.
This relay is turned on to perform
coincidence output from CH1 coincidence
output No.1 and CH1 coincidence output
No.2 terminals.
The command is valid while this relay is
on.
UNewLCPU
SM1893
CH1 preset
command
Presets the counter
value.
This relay is turned on to preset the
counter value.
The command is valid at the rise of this
relay (off on).
The on and off time must be held for at
least 2ms.
UNewLCPU
SM1894
CH1 count down
command
Counts down pulses.
This relay is turned on to count down
pulses.
The command is valid while the Pulse
input mode is either 1-phase multiple of n
or 1-phase multiple of n (A phase only).
The command is valid while this relay is
on.
UNewLCPU
SM1895
CH1 count
enable
command
Starts counting.
This relay is turned on to start counting.
The command is valid while this relay is
on.
UNewLCPU
SM1896
CH1 counter
function
selection start
command
Starts the selected
counter function.
This relay is turned on to start the
selected counter function.
When the count disabling function is
selected, the command is valid while this
relay is on.
When the latch counter function or the
sampling counter function is selected, the
command is valid at the rise of this relay
(off on). The on time must be held for
at least 2ms.
When the count disabling/preset function
or the latch counter/preset function is
selected, the command is invalid.
UNewLCPU
SM1897
CH1 external
preset (phase Z)
request
detection reset
command
Resets CH1 external
preset (phase Z) request
detection.
This relay is turned on to reset CH1
external preset (phase Z) request
detection.
The command is valid at the rise of this
relay (off on).
The on and off time must be held for at
least 2ms.
UNewLCPU
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU

Table of Contents

Related product manuals