501
APPENDICES
A
Appendix 2 List of Special Relay Areas
SM1898
CH1 pulse
measurement
start command
Starts pulse
measurement.
This relay is turned on to measure pulses.
The command is valid while this relay is
on.
UNewLCPU
SM1899
CH1 error reset
command
Resets the CH1 error.
This relay is turned on to reset the CH1
error.
The command is valid at the rise of this
relay (off on).
The on and off time must be held for at
least 2ms.
UNewLCPU
SM1900
CH2 counter
value greater
(No.1)
OFF: Coincidence point
(No.1) or smaller
ON: Greater than
coincidence point
(No.1)
This relay turns on when "current value of
CH2 > coincidence output No.1 point
setting value" is met.
This relay turns off when "current value of
CH2 coincidence output No.1 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1901
CH2 counter
value
coincidence
(No.1)
OFF: Not detected
ON: Detected
This relay turns on when "current value of
CH2 = coincidence output No.1 point
setting value" is met.
This relay is turned off by turning on CH2
coincidence signal No.1 reset command.
S (Status
change/
Every END
processing)
New LCPU
SM1902
CH2 counter
value smaller
(No.1)
OFF: Coincidence point
(No.1) or greater
ON: Smaller than
coincidence point
(No.1)
This relay turns on when "current value of
CH2 < coincidence output No.1 point
setting value" is met.
This relay turns off when "current value of
CH2 coincidence output No.1 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1903
CH2 counter
value greater
(No.2)
OFF: Coincidence point
(No.2) or smaller
ON: Greater than
coincidence point
(No.2)
This relay turns on when "current value of
CH2 > coincidence output No.2 point
setting value" is met.
This relay turns off when "current value of
CH2 coincidence output No.2 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1904
CH2 counter
va
lue
coincidence
(No.2)
OFF: Not detected
ON: Detected
This relay turns on when "current value of
CH2 = coincidence output No.2 point
setting value" is met.
This relay is turned off by turning on CH2
coincidence signal No.2 reset command.
S (Status
change/
Every END
processing)
New LCPU
SM1905
CH2 counter
value smaller
(No.2)
OFF: Coincidence point
(No.2) or greater
ON: Smaller than
coincidence point
(No.2)
This relay turns on when "current value of
CH2 < coincidence output No.2 point
setting value" is met.
This relay turns off when "current value of
CH2 coincidence output No.2 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1906
CH2 external
preset (phase Z)
request
detection
OFF: Not detected
ON: Detected
This relay turns on when a preset request
by phase Z (preset) terminal of CH2 is
detected.
This relay is turned off by turning on CH2
external preset (phase Z) request
detection clear command.
S (Every
END
processing)
New LCPU
SM1907 CH2 Error
OFF: No error
ON: Error
This relay turns on if the CH2 error
occurs.
This relay turns off when an error cause is
removed and CH2 error reset command is
turned on.
S (Every
END
processing)
New LCPU
SM1908 CH2 warning
OFF: No warning
ON: Warning
This relay turns on if a warning occurs in
CH2.
This relay turns off when a warning cause
is removed and CH2 error reset command
is turned on.
S (Every
END
processing)
New LCPU
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU

Table of Contents