501
APPENDICES
A
Appendix 2 List of Special Relay Areas
SM1898
CH1 pulse
measurement
start command
Starts pulse
measurement.
• This relay is turned on to measure pulses.
• The command is valid while this relay is
on.
UNewLCPU
SM1899
CH1 error reset
command
Resets the CH1 error.
• This relay is turned on to reset the CH1
error.
• The command is valid at the rise of this
relay (off on).
• The on and off time must be held for at
least 2ms.
UNewLCPU
SM1900
CH2 counter
value greater
(No.1)
OFF: Coincidence point
(No.1) or smaller
ON: Greater than
coincidence point
(No.1)
• This relay turns on when "current value of
CH2 > coincidence output No.1 point
setting value" is met.
• This relay turns off when "current value of
CH2 coincidence output No.1 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1901
CH2 counter
value
coincidence
(No.1)
OFF: Not detected
ON: Detected
• This relay turns on when "current value of
CH2 = coincidence output No.1 point
setting value" is met.
• This relay is turned off by turning on CH2
coincidence signal No.1 reset command.
S (Status
change/
Every END
processing)
New LCPU
SM1902
CH2 counter
value smaller
(No.1)
OFF: Coincidence point
(No.1) or greater
ON: Smaller than
coincidence point
(No.1)
• This relay turns on when "current value of
CH2 < coincidence output No.1 point
setting value" is met.
• This relay turns off when "current value of
CH2 coincidence output No.1 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1903
CH2 counter
value greater
(No.2)
OFF: Coincidence point
(No.2) or smaller
ON: Greater than
coincidence point
(No.2)
• This relay turns on when "current value of
CH2 > coincidence output No.2 point
setting value" is met.
• This relay turns off when "current value of
CH2 coincidence output No.2 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1904
CH2 counter
va
lue
coincidence
(No.2)
OFF: Not detected
ON: Detected
• This relay turns on when "current value of
CH2 = coincidence output No.2 point
setting value" is met.
• This relay is turned off by turning on CH2
coincidence signal No.2 reset command.
S (Status
change/
Every END
processing)
New LCPU
SM1905
CH2 counter
value smaller
(No.2)
OFF: Coincidence point
(No.2) or greater
ON: Smaller than
coincidence point
(No.2)
• This relay turns on when "current value of
CH2 < coincidence output No.2 point
setting value" is met.
• This relay turns off when "current value of
CH2 coincidence output No.2 point
setting value" is met.
S (Every
END
processing)
New LCPU
SM1906
CH2 external
preset (phase Z)
request
detection
OFF: Not detected
ON: Detected
• This relay turns on when a preset request
by phase Z (preset) terminal of CH2 is
detected.
• This relay is turned off by turning on CH2
external preset (phase Z) request
detection clear command.
S (Every
END
processing)
New LCPU
SM1907 CH2 Error
OFF: No error
ON: Error
• This relay turns on if the CH2 error
occurs.
• This relay turns off when an error cause is
removed and CH2 error reset command is
turned on.
S (Every
END
processing)
New LCPU
SM1908 CH2 warning
OFF: No warning
ON: Warning
• This relay turns on if a warning occurs in
CH2.
• This relay turns off when a warning cause
is removed and CH2 error reset command
is turned on.
S (Every
END
processing)
New LCPU
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU