FX1N Series Programmable Controllers Outputs 6.
6-3
1
2
3
4
5
6
7
6.2.1 Reliability Tests
The test results in the table below were gathered from a 1 sec ON/OFF test cycle. Please note
that the over current induced by in-rush greatly reduces the relay contact’s service life. The
rated life for an inductive AC load such as a conductor or solenoid valve is 500,000 operations
at 20VA.
20VA 35VA 80VA
Load capacity
0.2A/100VAC
0.1A/200VAC
0.35A/100V AC
0.17A/240V AC
0.8A/100V AC
0.4A/240V AC
Life of contact (cycles) 3,000,000 1,000,000 200,000
Example load (Mitsubishi contactor) S-K10 ~ S-K95 S-K100 ~ S-K150 S-K180,S-K400