10 Buffer Memory
10.8 [BFM#352 to #383] Remote Output (RY)
110
FX3U-16CCL-M User's Manual
10.8 [BFM#352 to #383] Remote Output (RY)
Used when the remote net ver. 1 mode or remote net additional mode is selected.
The output status from remote I/O stations, remote device stations and intelligent device stations are stored.
Each station uses 2 words.
Caution
• When the TO instruction (or direct buffer memory specification) is executed for writing to an area without
assigned link points, writing is invalid.
When the FROM instruction (or direct buffer memory specification) is executed for reading from an area
without assigned link points, the reading operation results in "0" being read.
• The last two bits cannot be used in the communication between the master and intelligent device stations.
• The upper 16bits (1 word) in the last station of remote stations and intelligent device stations is occupied
as a system area. For details, refer to the each unit's manuals.
RY F to RY 0
RY 1F to RY 10
RY 2F to RY 20
RY 3F to RY 30
RY 4F to RY 40
RY 5F to RY 50
RY 6F to RY 60
RY 7F to RY 70
RY 8F to RY 80
RY 9D to RY 90
RY1EF to RY1E0
RY1FF to RY1F0
to
Remote output (RY)
160H
161H
162H
163H
164H
165H
166H
167H
168H
169H
17FH
17DH
17EH
For station
No. 1
For station
No. 2
For station
No. 3
For station
No. 4
For station
No. 5
For station
No. 16
Y0F to Y00
Y1F to Y10
RY F to RY 0
RY 1F to RY 10
BFM No.
to
RY 2F to RY 20
RY 3F to RY 30
RY 4F to RY 40
RY 5F to RY 50
RY 6F to RY 60
RY 7D to RY 70
RY1DF to RY1D0
: The last two bits cannot be used in the communication between the master and intelligent device stations.
(In the example above, RY9E and RY9F cannot be used.)
Remote output (RY)
Master station
Remote I/O station
(Station No. 1:
Occupies 1 station)
Remote device station/
Intelligent device station
(Station No. 2:
Occupies 4 stations)