14 Example of Communication between Master Station
14.1 When Remote Net Ver. 1 Mode is Used
180
FX3U-16CCL-M User's Manual
• Program to control intelligent device stations (FX3U-64CCL)
Unit
error
M20
M35
Unit
ready
Reads the data link status
in intelligent device station
(SW0080).
M21
Data link
status in
master
station
M501
Y030
Y031
There is an error in
data link in the FX
3U-
64CCL. (Station No. 1)
Data link is being
executed in the FX
3U-
64CCL. (Station No. 1)
Data link is being
executed in the FX
3U-
64CCL. (Station No. 3)
FNC 79
FROM
K0 H0680 K4M501 K1
M501
M503
M503
Normal link (station No. 1)
Link error (station No. 1)
Normal link (station No. 3)
Link error (station No. 3)
FNC 01
CALL
P10
FNC 01
CALL
P20
FNC 06
FEND
Program for
communication
ith the FX3U-
64CCL (Station
No. 1).
P10
There is an error in
data link in the FX
3U-
64CCL. (Station No. 3)
To the next page
M21
Data link status in
master station
Y040
Master station data link
error
M8000
RUN monitor
FNC 79
FROM
K0 H00E0 K4M100 K4
FNC 78
TO
K0 H0160 K4M300 K4
FNC 78
TO
K0 H01E0 D100 K8
Reads from remote input.
HE3 to HE0
(RX3F to RX0)
M163 to M100
FNC 79
FROM
K0 H02E0 D200 K8
Reads from remote
register (RWr).
H2E7 to H2E0
(RWr7 to RWr0)
D207 to D200
M100
FX
3U
-64CCL (RX00)
When RX00 in the
FX
3U-64CCL
(station No. 1) turns ON,
Y000 in the PLC turns ON.
Y000
X000
When X000 in the PLC
turns ON, RY00 in the
FX
3U-64CCL
(station No. 1) turns ON.
M300
Program for
confirming
operation of the
FX
3U-64CCL
(Station No. 1).
FNC 02
SRET
Writes to remote output.
M363 to M300
H163 to H160
(RY3F to RY0)
Writes to remote register
(RWw).
D107 to D100
H1E7 to H1E0
(RWw7 to RWw0)