B-58
FX Series PLC User's Manual - Data Communication Edition
N:N Network
10 Related Data
10.2 Details of Related Devices
2. Detailed contents
1) The device used varies depending on the FX Series.
2) Error code list
M: Master station, L: Slave station
*1. Any slave station other than the slave station in which error occurred
*2. Station in which error occurred
3. Cautions on use
Data transfer sequence errors that occurred within the station itself cannot be detected.
Do not change the preset numeric value using a program or programming tool.
FX Series
Master 
station
Slave 
station 
No. 1
Slave 
station 
No. 2
Slave 
station 
No. 3
Slave 
station 
No. 4
Slave 
station 
No. 5
Slave 
station 
No. 6
Slave 
station 
No. 7
FX
1N, FX2N, FX3U, 
FX
1NC, FX2NC, FX3UC
D8211 D8212 D8213 D8214 D8215 D8216 D8217 D8218
FX
0N, FX1S D211 D212 D213 D214 D215 D216 D217 D218
Error 
code
Error name
Station 
in which 
error 
occurred
Station 
which 
detected 
error
Contents of error Check point
01H Monitoring timeout L M
Slave station did not respond to the
sending request from the master station
within the monitoring time.
Wiring and power 
supply
02H
Station number 
error
LM
An unexpected slave station responded
to the sending request by the master
station.
Wiring
03H Counter error L M
The counter value included in the
parameter data is different from the
counter value given by a slave station.
Wiring
04H
Message format 
error
LM, L
The message given by the slave station
is incorrect.
Wiring, power 
supply and station 
number settings
11H Monitoring timeout M L
The master station did not give a sending
request to the next slave station within
the monitoring timer.
Wiring and power 
supply
14H
Message format 
error
ML
The message from the master station is
incorrect.
Wiring, power 
supply and station 
number settings
21H
Slave station no 
response error
L
L
*1
The specified slave station does not exist.
Wiring, power 
supply and station 
number settings
22H
Station number 
error
L
L
*1
An unexpected slave station responded
to the sending request by the master
station.
Wiring
23H Counter error L
L
*1
The counter value included in the
parameter data is different from the
counter value given by a slave station.
Wiring
31H 
Parameter not 
received
L
L
*2
Before parameters had been received,
sending request was received from the
master station.
Wiring and power 