D-30
FX Series PLC User's Manual - Data Communication Edition
Computer Link
4 Wiring
4.5 Connection Diagram for RS-485 and RS-422
4.5 Connection Diagram for RS-485 and RS-422
4.5.1 One-pair wiring
4.5.2 Two-pair wiring
 
Terminal
resistor:
110 
Ω
Class-D grounding
(resistance: 100 
Ω
 or less)
*1
Class-D grounding
(resistance: 100 
Ω
 or less)
*1
FX
2NC
-485ADP
SDA
SDB
RDA
RDB
SG
FX
3U
-485-BD
FX
2N
-485-BD
FX
1N
-485-BD
FX
3U
-485ADP(-MB)
SDA
SDB
RDA
RDB
SG
FX
0N
-485ADP
SDA
SDB
RDA
RDB
LINK
SG
FG
*2
Terminal
resistor:
110 
Ω
Communication
equipment operating
in accordance with
RS-485
SDA
SDB
RDA
RDB
LINK
SG
*3 *3
Make sure to perform Class-D grounding to the shield of a twisted pair cable connected to the FX
2N
-485-BD, FX
1N
-485-BD,
FX
3U
-485-BD, FX
2NC
-485-ADP or FX
3U
-485ADP(-MB).
Make sure to connect the   terminal to the   (grounding) terminal in the PLC requiring Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
Make sure to provide a terminal resistor at the end of each line.
The FX
3U
-485-BD and FX
3U
-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch accordingly.
The FX
0N
-485ADP, FX
2NC
-485ADP, FX
2N
-485-BD and FX
1N
-485-BD are supplied together with terminal resistors.
*1
*2
*3
FG
Terminal
resistor:
330 
Ω
×
 2
Class-D grounding
(resistance: 100 
Ω
 or less)
*1
Class-D grounding
(resistance: 100 
Ω
 or less)
*1
FX
2NC
-485ADP
SDA
SDB
RDA
RDB
SG
FX
3U
-485-BD
FX
2N
-485-BD
FX
1N
-485-BD
FX
3U
-485ADP(-MB)
SDA
SDB
RDA
RDB
SG
FX
0N
-485ADP
SDA
SDB
RDA
RDB
LINK
SG
FG
*2
Terminal
resistor:
330 
Ω
×
 2
Communication
equipment operating
in accordance with
RS-485/RS-422
SDA
SDB
RDA
RDB
LINK
SG
*3 *3
*3 *3
Make sure to perform Class-D grounding to the shield of a twisted pair cable connected to the FX
2N
-485-BD, FX
1N
-485-BD,
FX
3U
-485-BD, FX
2NC
-485-ADP or FX
3U
-485ADP(-MB).
Make sure to connect the   terminal to the   (grounding) terminal in the PLC requiring Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
Make sure to provide a terminal resistor at the end of each line.
The FX
3U
-485-BD and FX
3U
-485ADP(-MB) have a built-in terminal resistor.
Set the terminal resistor selector switch accordingly.
The FX
0N
-485ADP, FX
2NC
-485ADP, FX
2N
-485-BD and FX
1N
-485-BD are supplied together with terminal resistors.
*1
*2
*3
FG