E-101
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
11 Troubleshooting
11.6 Error Codes
A
Common Items
B
N:N Network
C
Parallel Link
D
Computer Link
E
Inverter
Communication
F
Non-Protocol
Communication
(RS/RS2 Instruction)
G
Non-Protocol
Communication 
(FX
2N
-232IF)
H
Programming
Communication
I
Remote 
Maintenance
Apx.
Discontinued
models
266 Mode error
Inverter sent the error code HA.
A parameter was written in a mode other than computer link mode,
or while the inverter was operating.
Inverter does 
not accept 
received data, 
but is not 
brought to an 
alarm stop.
267 Instruction code error
Inverter sent the error code HB.
Non-existing instruction code was specified.
268 Data range error
Inverter sent the error code HC.
In writing a parameter or operation frequency, data outside the
allowable range was specified.
269 Undefined
Inverter sent the error code HD.
Not defined currently in inverter.
270 Undefined
Inverter sent the error code HE.
Not defined currently in inverter.
271 Undefined
Inverter sent the error code HF.
Not defined currently in inverter.
Error 
code
Contents of error
Inverter 
operation