4. OPERATING RANGE
1) POWER SUPPLY
2) OPERATION
5. OUTLET AIR SPEED AND COVERAGE RANGE
The air coverage range is the value up to the position where the air speed is 0.8ft/sec. when air is blown out
horizontally from the unit at the High fan setting.
The coverage range should be used only as a general guideline since it varies according to the size of the
room and furniture installed inside the room.
6. ADDITIONAL REFRIGERANT CHARGE (R22 (OZ))
Indoor unit
Outdoor unit
Rating
115V 1 phase 60Hz
208/230V 1 phase 60Hz
Allowable voltage
Min. 103V — Max. 127V
Min. 198V — Max. 253V
Function
Cooling
DB (˚F)
80
95
67
80
Condition
Standard temperature
Maximum temperature
Minimum temperature
Maximum humidity
Indoor
Intake air temperature
Outdoor
WB (˚F)
67
71
57
75
DB (˚F)
95
115
0
80
WB (˚F)
75
75
75
Airflow
Air speed
Coverage range
(CFM)
(ft / sec.)
(ft)
Standard
height
(8.2ft)
PK18FL3
710
16.1
41
PK24FL3
710
16.1
41
PK30FL3
990
17.7
50
PK36FL3
990
17.7
50
Model
PK18FL3
PK24FL3
PK30FL3
PK36FL3
5 lbs 8 oz
9 lbs 15 oz
10 lbs 2 oz
10 lbs 9 oz
25ft
0
0
0
0
40ft
0
0
0
0
55ft
0
0
0
0
70ft
0
0
0
0
85ft
0
0
0
0
100ft
0
0
0
0
115ft
2
2
5
5
130ft
4
4
10
10
150ft
7
16
16
164ft
9
20
20
Outdoor unit
precharged
(up to 100ft)
Refrigerant piping length (over way)
OC275--1.qxp 01/12/14 3:06 PM Page 11