[ VIII Test Run Mode ]
- 112 -
HWE1018A GB
[7] Standard Operation Data (Reference Data)
(1) Cooling operation
Operation
Indoor unit model Outdoor unit model
PFD-P500VM-E PUHY-P250YJM-A x 2
Operat-
ing condi-
tions
Ambient
tempera-
ture
Indoor
DB/
WB
27°C/19°C [81°F/66°F]
Outdoor 35°C/- [95°F/-]
Piping Total pipe length m[ft] 7.5 [24-9/16]
Outdoor
unit
Compressor frequency Hz 56
LEV
opening
Indoor unit
Pulse
700
SC (LEV1) 105
Pressure
Pressure High pressure (after O/S)
/low pressure (before accumulator)
MPa
[psi]
2.90/0.99 [421/144]
Temp. of
each sec-
tion
Outdoor
unit
Discharge(TH4)
°C
[°F]
76 [169]
Heat exchanger outlet
(TH3)
40 [104]
Compressor inlet 22 [72]
Compressor shell bottom 36 [97]
SC heat exchanger outlet
(TH6)
24 [75]
Bypass outlet (TH2) 14 [57]
Indoor unit
LEV inlet 22 [72]
Heat exchanger outlet 18 [64]