[ VI Refrigerant Circuit ]
- 70 -
HWE1018A GB
[2] Principal Parts and Functions
1. Outdoor unit
Part
name
Symbols
(functions)
Notes Usage Specifications Check method
Com-
pressor
MC1
(Comp1)
Adjusts the amount of circulating
refrigerant by adjusting the operat-
ing frequency based on the oper-
ating pressure data
250 models
Low-pressure shell scroll
compressor
Wirewound resistance
20°C[68°F] : 0.981ohm
High
pres-
sure
sensor
63HS1 1) Detects high pressure
2) Regulates frequency and pro-
vides high-pressure protec-
tion
Low
pres-
sure
sensor
63LS 1) Detects low pressure
2) Provides low-pressure pro-
tection
Pres-
sure
switch
63H1 1) Detects high pressure
2) Provides high-pressure pro-
tection
4.15MPa[601psi] OFF setting