EasyManua.ls Logo

Mitsubishi PUHY-P250YJM-A - Page 134

Mitsubishi PUHY-P250YJM-A
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[ IX Troubleshooting ]
- 125 -
HWE1018A GB
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to com-
pressor inverter on fan inverter.
Example
Code 4225 (detail code 108): Bus voltage drop in the fan inverter system
Code 4230 : Heatsink overheat protection in the compressor inverter system
The last digit Inverter system
0 or 1 Compressor inverter system
5 Fan inverter system

Table of Contents

Related product manuals