EasyManua.ls Logo

Mitsubishi PUHY-P250YJM-A - Page 236

Mitsubishi PUHY-P250YJM-A
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[ X LED Monitor Display on the Outdoor Unit Board ]
- 227 -
HWE1018A
Data before error
No.
SW1
Item
Display
Unit
(A, B)
*1
Remarks
1234567890 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8 OC OS
201 1001001100
Outdoor unit operation
status
20-second
restart mode
Compressor
in operation
Preliminary
error
Error
20-second
restart after
instanta-
neous power
failure
Preliminary
low pres-
sure error
AA
202 0101001100 OC/OS identification OC/OS-1 A A
203 1101001100
204 0011001100
205 1011001100
Outdoor unit Operation
mode
Permissible
stop
Standby Cooling Heating
Dehumidify-
ing operation
B
206 0111001100
207 1111001100
208 0000101100
Outdoor unit control
mode Stop Thermo OFF
Abnormal
stop
Scheduled
control
Initial start
up
Defrost Oil balance
Low fre-
quency oil
recovery
AA
209 1000101100
Refrigerant
recovery
AA
210 0100101100
211 1100101100
Relay output display 1
Lighting
Comp in op-
eration
72C OC Always lit A A
212 0010101100
Relay out-
put display
2
Lighting
Top 21S4a CH11 SV1a
AA
Bottom
21S4b SV5b
213 1010101100
Relay out-
put display
3
Lighting
Top Lit while
power to the
indoor units
is being sup-
plied
AA
Bottom SV9
214 0110101100
215 1110101100
*1 A: The condition of either OC or OS is displayed individually. B: The condition of the entire refrigerant system is displayed.

Table of Contents