7 - 7 7 - 7
MELSEC-Q
7 PARAMETER SETTING
(2) GX Developer connection information setting
Address Parameter Name Setting Range Initial Value
0030H
(48)
Number of TCP connections for GX Developer connection 0 to 8 1
(3) MODBUS
R
/TCP setting
Address Parameter Name Setting Range Initial Value
0110H
(272)
Local slave station port No.
1 to 4999,
5020 to
65535
(
*
1)
502
0111H
(273)
Target slave port No. for automatic communication function
1 to 65535
(
*
1)
502
0114H
(276)
CPU response monitoring timer value
Set time = set value
500ms
1 to 2400 10
0115H to 0116H
(277 to 278)
IP address
Refer to Section
7.2.4 (4) (b)
00000000
H
0117H
(279)
Preferred node specification 1
Number of
connections
0 to 64 0
0118H to 01D4H
(280 to 468)
Preferred node specification 2 to 64 (Same as Preferred node specification 1)
*1: When specifying a value of 32768 (8000H) or more in a sequence program,